What IEC 62443 is
The series is developed jointly by ISA99 and IEC TC 65, which is why it is often written ISA/IEC 62443. It covers the cybersecurity of industrial automation and control systems (IACS) not from the angle of one product but across the whole lifecycle and three roles:
- Asset owner: the plant that operates the installation.
- Service provider: the system integrator and the maintenance organisation.
- Product supplier: the maker of a controller, an application or a network device.
That split is the key to the whole series. Most confusion comes from reading a part written for a different role.
The four groups of parts
- 62443-1-x, general. Concepts, models and terminology. Part 1-1 introduces the base definitions, including zones, conduits and security levels.
- 62443-2-x, policies and procedures. Part 2-1 describes the security programme for the asset owner. Part 2-3 covers patch management, and 2-4 the requirements for service providers, meaning integrators and maintenance.
- 62443-3-x, system. Part 3-1 reviews security technologies. Part 3-2 covers risk assessment and the division of an installation into zones and conduits. Part 3-3 holds the system security requirements together with the security levels.
- 62443-4-x, component. Part 4-1 is the secure product development lifecycle at the vendor. Part 4-2 is the technical requirements for individual components: controllers, applications, network devices and workstations.
Individual parts have their own editions and are revised over time, so when citing a specific requirement it is worth checking the current edition in the IEC webstore.
Which part to read
- A plant: 62443-2-1 (security programme), 62443-3-2 (zones, conduits and risk assessment), 62443-3-3 (system requirements, which can go straight into a tender specification).
- An integrator or maintenance provider: 62443-2-4 (requirements on the service provider), 62443-3-3, and 62443-4-2 when selecting components.
- A device or software vendor: 62443-4-1 (development process) and 62443-4-2 (technical product requirements).
For a plant the practical order is 3-2, then 3-3, with 2-1 as the organisational frame. The risk assessment sets the zones and the target levels, and only then is it clear which requirements to look up.
Zones and conduits
A zone is a set of assets with common security requirements, such as a packaging line, a boiler control system or the office network. A conduit is a connection between zones, meaning every path data takes: a fibre link, a maintenance VPN, a firewall, and the technician's USB stick as well.
The exercise is not about drawings. Each zone gets a target security level, and each conduit becomes a place where requirements can be enforced. In practice the first attempt almost always surfaces connections nobody remembered: a vendor's service modem, a switch shared between two installations, an engineering workstation with access to everything.
The seven foundational requirements
The whole series rests on seven foundational requirements (FR), which the detailed requirements roll up into:
- Identification and authentication control (IAC): who and what connects to the system.
- Use control (UC): what is permitted once authenticated.
- System integrity (SI): whether software and data have been altered.
- Data confidentiality (DC): protecting information from being read by the wrong party.
- Restricted data flow (RDF): segmentation and control of traffic between zones.
- Timely response to events (TRE): detection, logging and response.
- Resource availability (RA): resistance to overload and recovery after a failure.
In OT the order of importance is often the reverse of IT: availability and integrity usually come before confidentiality, because a stopped process costs money immediately.
Security levels
The levels describe who the system should hold off, not how secure it is in the abstract:
- SL 1: protection against casual or coincidental violation.
- SL 2: against intentional violation using simple means, with low resources and generic skills.
- SL 3: against sophisticated means, with moderate resources and knowledge of industrial systems.
- SL 4: against sophisticated means, with extended resources and high motivation.
Three variants go with them, and they are the ones most often confused:
- SL-T (target): the level a zone should reach, taken from the risk assessment.
- SL-C (capability): the level a product or system can deliver when configured correctly.
- SL-A (achieved): the level actually reached in the running installation.
"We are SL 2" on its own says nothing. What carries meaning is "the packaging zone has SL-T 2, the chosen controller has SL-C 2, and the measurement after commissioning showed SL-A 1, because authentication was switched off during start up". The gap between SL-C and SL-A is usually the most interesting part of an assessment.
Certification: what can and cannot be certified
A product can be certified (against 4-1 and 4-2), as can a vendor's development process and a service organisation (against 2-4). Schemes exist for this, including ISASecure and programmes run by certification bodies.
There is no "62443 certificate for a plant" in the sense that an ISO 9001 certificate exists. An asset owner builds a security programme in line with 2-1 and can have it assessed, but that assesses the programme rather than stamping the installation. When a supplier says a device "complies with 62443", the useful follow up is specific: which part, what SL-C, and is there an independent certificate or only a self declaration.
IEC 62443, NIS2 and the Polish KSC act
The law does not name the standard. NIS2 requires measures appropriate to the risk, and 62443 is a recognised way of showing what that means in an industrial environment. In practice the pieces line up like this:
- a risk assessment and zone model under 3-2 serves as evidence of the risk analysis NIS2 requires,
- the requirements in 3-3 translate into concrete technical measures and into purchasing specifications,
- the requirements on integrators in 2-4 are a natural tool for the supply chain security obligation,
- 4-1 and 4-2 are increasingly the reference when assessing products, including in the context of EU rules on the cyber resilience of products.
Where to start
- Draw the zones and conduits for one installation, as it is rather than as designed. The exercise usually points at the largest risks by itself.
- Set SL-T for each zone from the consequences, not from ambition. SL 3 everywhere is expensive and rarely justified.
- Check the SL-C of the equipment already installed by asking the vendors directly.
- Measure the gap between SL-T and reality, and turn that into a plan.
- Put the requirements into the specification for the next project, because requiring is cheaper than retrofitting.
Liscere's OT security assessment follows the IEC 62443 method and ends with a list of findings ordered by risk to the process, with the evidence attached.
Questions
What is IEC 62443?
A series of standards for the cybersecurity of industrial automation and control systems, developed jointly by ISA99 and IEC TC 65 and often written ISA/IEC 62443. It is organised in four groups: general concepts (1-x), policies and procedures (2-x), system requirements (3-x) and component requirements (4-x), and it addresses asset owners, service providers and product suppliers separately.
Which part of IEC 62443 applies to a plant?
In practice three: 62443-3-2 for risk assessment and the division into zones and conduits, 62443-3-3 for the system security requirements, which can be written straight into a tender specification, and 62443-2-1 for the security programme itself. Integrators work to 2-4, and product vendors to 4-1 and 4-2.
What do SL-T, SL-C and SL-A mean?
SL-T is the target security level for a zone, taken from the risk assessment. SL-C is the capability a product or system can deliver when it is configured correctly. SL-A is the level actually achieved in the running installation. Saying a site is at SL 2 without naming the variant says very little, and the gap between SL-C and SL-A is usually where the real findings are.
Can a plant be certified to IEC 62443?
Products, vendor development processes and service organisations can be certified, through schemes such as ISASecure. An asset owner builds a security programme in line with 62443-2-1 and can have it assessed, but there is no plant certificate in the sense of ISO 9001. When a supplier claims compliance, ask which part, what SL-C, and whether there is an independent certificate or only a self declaration.
Does IEC 62443 help with NIS2?
The law does not name the standard, but NIS2 requires measures appropriate to the risk, and 62443 is a recognised way of showing what that means in an industrial environment. A zone model under 3-2 evidences the risk analysis, the requirements in 3-3 become concrete technical measures, and 2-4 supports the supply chain obligation.
Sources
- IEC, the IEC 62443 series in the cybersecurity guidelines: syc-se.iec.ch
- IEC Webstore, current editions of each part: webstore.iec.ch
- ISA Global Cybersecurity Alliance, material on the ISA/IEC 62443 series: gca.isa.org
- ISASecure, the certification scheme for products and suppliers: isasecure.org